Mine Heating Unit
PRODUCT PARAMETERS
Installation and Operating Instructions for the Mine Heating Unit
- Sufficient space must be left around the installation position of the unit, especially at the heating-medium pipe connections and the access door, for installation and maintenance of the unit.
- The unit should be placed on a cement or steel base 100-200 mm higher than the machine room floor.
- Control valves and a steam trap (for steam) should be installed at the external heating-medium pipe connections, and the pipes should be supported by brackets; take care not to damage the heat exchanger during connection. An air vent should be provided at the highest point of the water inlet, and a drain point at the lower part of the water outlet. Pay attention to draining the water in the heater when it is out of use in winter, to prevent freeze cracking.
- The unit power supply is 380V, 50Hz. When wiring the power supply, check whether the fan impeller rotation direction complies with the rotation mark.
- The heating medium should be softened water or steam meeting the requirements; the working pressure of the heat exchanger is below 0.4 MPa.
- The unit should be operated and managed by professional personnel; check the operating condition frequently, and handle any abnormality promptly or stop the unit for troubleshooting.
- After one month of operation, comprehensively check whether all connecting fasteners are loose; if found, readjust and tighten them.
- After two years of operation, a comprehensive inspection, maintenance and servicing should be performed: focus on checking the heat exchanger and the heating-medium piping system, removing scale and dust on the heat exchanger surface.
- When the air volume required by the project exceeds 50,000 m3/h, multiple units can be connected in parallel, or a non-standard design can be made.
Description
The mine heating unit is a heating and ventilation device specially developed for industrial and mining enterprises and institutions, an upgraded replacement of the traditional air heater. The equipment mainly solves the problem of possible freezing at mine shaft openings or in factory workshops when winter temperatures are too low, keeping the working environment above 2 degrees C to effectively prevent freezing and ensure safe production. The unit adopts a frame structure, consisting of panels, an aluminum alloy frame, a heater, an axial fan, an intake air filter, an outlet regulating valve and a simple power distribution cabinet. The panels are color steel sheets (blue or white) with a thickness of 0.4 mm, with 50 mm polyurethane insulation board in the middle; the bottom is welded from channel steel. The unit is suitable for ventilation and heating in various industrial and mining enterprises, with a heating medium of 0.20.4 MPa steam or 95130 degrees C hot water. The structural design is reasonable, featuring convenient installation, stable performance, easy use and management, obvious energy-saving effect, attractive appearance and long service life.
Equipment Selection
Example: KJZ-50/40-S-Z denotes a hot-water mine heating unit with an outlet air temperature of 40 degrees C and an air volume of 50,000 m3/h, with left-side pipe connection. Calculation of the required air volume for the heater outlet temperature: for a total mine air volume of 200 m3/s, i.e. 720,000 m3/h, a minimum ambient temperature of -25 degrees C, an outlet air temperature of 40 degrees C and a standard shaft inlet air temperature of 2 degrees C, the calculated required air volume is about 299,077 m3/h (heating capacity about 390,000 m3/h). Based on the calculated air volume, eight mine heating units of 50,000 m3/h air volume can be selected to fully meet the above parameter requirements. That is, equipment selection: mine heating unit KJZ-50/25/40.
FAQs
We are a manufacturer of ventilation, air-conditioning, dust-removal and smoke-exhaust equipment. Our range covers fire smoke-exhaust fans, fire dampers and smoke-exhaust valves, aluminium air outlets and diffusers, ventilation ductwork and silencers, air-handling and fresh-air units, water tanks, cooling towers, seismic supports, and air-purification and kitchen oil-fume purification equipment.
Yes. Our fire dampers, smoke-exhaust fire dampers, smoke-exhaust valves and fire smoke-exhaust fans carry CCCF (3C) certification. For every fire-protection product we can supply national-level fire test reports together with the complete CCCF documentation package.
The company is certified to ISO 9001 (quality), ISO 14001 (environmental) and ISO 45001 (occupational health and safety) management systems, and holds AAA-grade certificates as a quality-assured, contract-honouring enterprise.
Our fan series includes CCCF axial fire smoke-exhaust fans, CCCF centrifugal fan boxes for fire service, pressurization supply fans, diagonal-flow fans, mixed-flow fans, axial fans, ceiling-mounted and floor-standing fresh-air ventilators, heat-recovery units, and finned-tube, rotary-wheel and heat-pipe air-handling units.
Dampers: CCCF automatic fire dampers, CCCF automatic smoke-exhaust fire dampers, CCCF automatic smoke-exhaust valves, manual balancing dampers, non-return dampers, pressurization supply outlets, multi-blade outlets, and CCCF smoke-exhaust outlets. Aluminium outlets: spherical jet nozzles, swirl diffusers, ceiling diffusers, weatherproof louvers, and single/double-deflection louvers.